Knowledge Base › Fluid Systems Error Case › Gutter Water Backflowing Indoors with a Siphon Roof Drain

Gutter Water Backflowing Indoors with a Siphon Roof Drain

E44-142 · Siphon and Backflow · Factory Siphon Rainwater System · ★★★

Problem Description

After a rainstorm the residual siphon pressure makes the gutter's standing water backflow through the access opening into the room, soaking the ceiling

Root Cause

[Residual Pressure] After the rain stops, the negative pressure in the pipe draws the gutter's remaining water back.
[Backflow] The standing water crosses the access opening into the room.
[Design Omission] No vent pipe to break the negative pressure and insufficient gutter capacity, so backflow occurred.

Corrective Solution

1) Provide an air-admitting vent pipe at the roof drain to break the negative pressure, because the negative pressure draws back the remaining water, thereby venting to stop the suction;
2) Verify and enlarge the gutter capacity against the return period, because insufficient capacity overflows, thereby enlarging to prevent overflow;
3) Provide a water seal at the access opening to prevent backflow, because the opening lets it in, thereby isolating with the water seal;
4) Provide inspection openings on the stack for clearing blockages, because a blockage disrupts the negative pressure, thereby allowing cleaning;
5) Review the roof slope and drainage grading, because a gentle slope ponds water, thereby grading it for free drainage;
6) Set the overflow opening low to prevent indoor flooding, because extreme rainstorms overflow, thereby overflowing outdoors;
7) Commission after a rainstorm and verify there is no backflow, because the design requires measurement, thereby confirming at delivery;
8) Include the vent pipe and gutter capacity in the design, because the original lack of venting is the root cause of backflow, thereby the design must include it.

Checklist

Reference

GB/T 50015-2019 Code for Design of Building Water Supply and Drainage