E44-142 · Siphon and Backflow · Factory Siphon Rainwater System · ★★★
After a rainstorm the residual siphon pressure makes the gutter's standing water backflow through the access opening into the room, soaking the ceiling
[Residual Pressure] After the rain stops, the negative pressure in the pipe draws the gutter's remaining water back.
[Backflow] The standing water crosses the access opening into the room.
[Design Omission] No vent pipe to break the negative pressure and insufficient gutter capacity, so backflow occurred.
1) Provide an air-admitting vent pipe at the roof drain to break the negative pressure, because the negative pressure draws back the remaining water, thereby venting to stop the suction;
2) Verify and enlarge the gutter capacity against the return period, because insufficient capacity overflows, thereby enlarging to prevent overflow;
3) Provide a water seal at the access opening to prevent backflow, because the opening lets it in, thereby isolating with the water seal;
4) Provide inspection openings on the stack for clearing blockages, because a blockage disrupts the negative pressure, thereby allowing cleaning;
5) Review the roof slope and drainage grading, because a gentle slope ponds water, thereby grading it for free drainage;
6) Set the overflow opening low to prevent indoor flooding, because extreme rainstorms overflow, thereby overflowing outdoors;
7) Commission after a rainstorm and verify there is no backflow, because the design requires measurement, thereby confirming at delivery;
8) Include the vent pipe and gutter capacity in the design, because the original lack of venting is the root cause of backflow, thereby the design must include it.
GB/T 50015-2019 Code for Design of Building Water Supply and Drainage