E44-194 · Siphon and Backflow · Cooling Tower Return Water · ★★
Siphon-type return water drains the basin, starving the pump
[Drainage] The siphon keeps drawing water from the basin.
[Pump Starvation] The basin runs empty and the pump sucks air.
[Design Omission] No siphon breaking, no water-level control, so it ran dry.
1) Install a vacuum breaker valve on the siphon return water to prevent drainage, because the siphon keeps drawing basin water and starves the pump, thereby breaking the vacuum to regulate it;
2) Provide low-level pump-stop protection for the basin, because an empty basin starves the pump, thereby stopping at low level;
3) Slope the return pipe to prevent full-pipe siphoning, because a full pipe starts a siphon, thereby keeping the slope free-flowing;
4) Install a level control valve to steady the basin level, because a changing level causes drainage, thereby regulating the level;
5) Interlock the pump inlet on level, because running dry damages it, thereby interlocking;
6) Periodically check the siphon state, because it strengthens gradually, thereby checking on schedule;
7) Commission and verify the basin is not drained and the pump does not run dry, because the design requires measurement, thereby confirming at delivery;
8) Include anti-drainage measures in the cooling tower return water, because the original lack of protection is the root cause of the drainage, thereby the design must include it.
GB/T 50102-2014 Code for Design of Industrial Circulating Water Cooling