E44-909 · Siphon and Backflow · Siphon Pipe · ★★
Air accumulation, weak suction, stoppage
[Mechanism] A local sag at the top of the pipe or a wrong slope direction traps gas, reducing the flow area and weakening the suction until the flow breaks.
[Calculation] The trapped gas pocket is 0.8 m long, 0.25 of the pipe diameter, raising the resistance 3-fold and dropping the flow 40% until it stops.
[Design Omission] No favorable slope, no high-point venting, and no slope-direction check.
1) Change to a favorable slope so that i≥0.003 (originally adverse, with sag points trapping air), because a favorable slope lets air drain with the flow and removes the sag points, thereby venting and restoring suction;
2) Install automatic vent valves at the high points (venting as soon as air accumulates), because a trapped gas pocket blocks the flow and venting restores it, thereby eliminating the pocket;
3) Raise and smoothly join the locally sagging sections (remove the dip), because dips are the source of air pockets and removing them leaves nowhere for air to collect, thereby making the pipe top smooth;
4) Raise the flow velocity to 1.3 m/s (originally 0.9 m/s), because at low velocity gas tends to float up and accumulate while higher velocity carries it out, thereby suppressing accumulation;
5) Provide a sight glass plus manual venting at the high points (as backup), because if the automatic valve fails manual venting is needed for double protection, thereby making venting independent of a single point;
6) Run an air-accumulation test (fill with water and check there are no air pockets), because the design missed the slope check and the test confirms the pocket is eliminated, thereby verifying venting is effective;
7) Monitor the flow during operation (alarm on a drop >20%), because air accumulation shows first as a flow drop, earlier than a break, thereby monitoring the flow for early warning;
8) Write the favorable slope and high-point venting into the installation checklist, because the root cause of air accumulation is an adverse slope with no venting, thereby the installation controls it to prevent weak flow and breaks.
GB/T 20801.3-2020 Design code for industrial metallic piping