E44-910 · Siphon and Backflow · Pump House · ★★★
Backflow, flooding, damage
[Mechanism] The pump-house floor is below the level of the external river/pond, so after the pump stops the medium flows back through the outlet into the pump house.
[Calculation] With an internal-to-external level difference of 2.5 m, the backflow follows orifice flow Q=μA√(2gΔH)≈0.3 m³/s and floods to a depth of 0.18 m in 10 min.
[Design Omission] The pump house was not raised, the outlet has no check valve, and no water stop was provided.
1) Raise the pump-house floor to 0.5 m above the external level (originally 2.5 m below), because a positive elevation difference eliminates backflow into the house and the 0.5 m margin guards against heavy rain, thereby preventing flooding by elevation;
2) Install a slow-closing check valve at the outlet (leakage ≤5 mL/min), because backflow enters the house through the outlet and the check valve cuts off the water path, thereby isolating the water source;
3) Provide a water-stop sill at the pump-house door (0.3 m high) plus a drainage pump (50 m³/h), because minor seepage still needs to be drained, the sill blocks it and the pump removes it, thereby providing double protection against flooding;
4) Provide level-interlocked shutoff on the outlet pipe (close the valve as soon as the house floods), because flooding shows first as a rise in level and the interlock cuts off immediately, thereby monitoring flooding and shutting off quickly;
5) Run a backflow flooding test (simulate the outlet open and check the house does not flood), because the design missed the elevation-difference check and the test confirms the elevation is sufficient, thereby setting the raise on data;
6) Install a level alarm inside the house (alarm >0.1 m), because flooding shows first as a level and earlier than equipment damage, thereby giving an early warning;
7) In the pump-stop sequence, close the outlet before stopping (interlock), because a wrong sequence causes backflow and controlling the sequence suppresses flooding, thereby controlling shutdown to prevent backflow;
8) Write the pump-house elevation and check valve into the pump-station specification, because the root cause of flooding is a low elevation with no isolation, thereby the specification controls it to prevent flooding.
GB/T 20801.3-2020 Design code for industrial metallic piping