Knowledge Base › Fluid Systems Error Case › Backflow Causing System Reverse Flow

Backflow Causing System Reverse Flow

E44-916 · Siphon and Backflow · System · ★★★

Problem Description

Reverse flow, back-feeding, disorder

Root Cause

[Mechanism] The system branches have unequal elevations, so after the pump stops the medium in a higher branch backflows into a lower branch and disrupts the system.
[Calculation] With a branch elevation difference of 1.5 m the reverse flow is v≈0.8 m/s and 0.5 m³/h, throwing the operating conditions into disorder.
[Design Omission] The branches had no check valves, the elevation difference was not checked, and there was no fast shutoff.

Corrective Solution

1) Install check valves at each branch inlet (tight shutoff, zero leakage), because the elevation difference drives inter-branch reverse flow and the check valves isolate one-way, thereby preventing a higher branch from surging into a lower one;
2) Check the inter-branch elevation difference so it decreases along the flow direction (the following branch lower than the preceding one), because a positive elevation difference eliminates the reverse driving force and the layout prevents reversal, thereby keeping the system orderly;
3) Provide fast shutoff in the critical branches (pneumatic ≤2 s) interlocked on pressure, because a sudden condition change causes reversal and fast shutoff limits the volume to <0.01 m³, thereby controlling the volume and reducing disorder;
4) Provide a header check valve plus a buffer tank on the system, because header reverse flow propagates through the whole system and the check valve cuts off the source while the tank absorbs and shaves it, thereby steadying the system;
5) Monitor the flow online (alarm on reverse flow), because reverse flow first shows as an abnormal flow direction before the full disruption, thereby monitoring the flow for early warning;
6) Perform a reverse-flow test (simulate a pump stop and verify the branches do not surge), because the design omitted the difference check and the test confirms the isolation effect, thereby verifying the isolation;
7) Control the operating branch differential pressure ≥0.05 MPa with an alarm, because a stable difference prevents reverse flow and controlling it prevents disorder, thereby preventing disturbance in operation;
8) Write the branch check valves and elevation-difference checking into the system regulations, because the root cause of reverse flow is a reversed difference without isolation, so the regulations must govern to prevent disturbance.

Checklist

Reference

GB/T 20801.3-2020 Design code for industrial metallic piping

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »