MOULDLKnowledge Base3D Model DownloadsMembership
中文版Model Store »
HomeModels
Table of contents

Knowledge Base Home

📐 Standard Data

🧮 Calculators

📖 Selection Guides

🏭 Material Grades

❓ Engineer FAQ

🗂 Quick-Reference Categories

❌ Error Case Studies

📚 Technical Articles

Knowledge Base › Fluid Systems Error Case › Vibration of a Siphon Pipe

Vibration of a Siphon Pipe

E44-917 · Siphon and Backflow · Siphon Pipe · ★★

Problem Description

Vibration, noise, loosening

Root Cause

[Mechanism] The unstable siphon flow regime and the movement of the two-phase gas-liquid segment cause piping vibration and loosen the supports and hangers.
[Calculation] The dominant vibration frequency f=2.3 Hz approaches the piping natural frequency of 2.5 Hz, the amplification factor reaches 8, and the amplitude exceeds 0.5 mm, loosening the supports.
[Design Omission] The support and hanger spacing was too large, frequency avoidance was not applied, and no damping was added.

Corrective Solution

1) Check the support and hanger spacing to keep the natural frequency away from the 2.3 Hz excitation (reduce the spacing from 4 m to 2.5 m to raise the natural frequency to 4 Hz), because frequency avoidance cuts the amplification factor from 8 to <2 and the amplitude to <0.1 mm, thereby eliminating resonance;
2) Add dampers to the piping (viscous damping ratio ≥0.08), because damping absorbs energy and shaves the vibration peak, reducing it by 70%, thereby suppressing vibration;
3) Remove the air to prevent the two-phase segment (high-point venting plus flow stabilization), because the moving gas-liquid segment is the excitation source and removing the air steadies the flow, thereby removing the vibration source;
4) Add a fixed support at the elbows (limit displacement), because the elbows carry large forces and loosen easily and fixing limits displacement, thereby preventing loosening;
5) Control the flow velocity at 1.2~1.5 m/s to stabilize the flow, because velocity fluctuation excites vibration and steady flow reduces it, thereby controlling the velocity and suppressing vibration;
6) Perform a vibration test (measure the amplitude ≤0.1 mm), because the design omitted frequency avoidance and the test confirms whether resonance occurs, thereby sizing the supports from data;
7) Tighten the support bolts to the specified torque and use lock nuts, because vibration loosens them and locking keeps them tight, thereby keeping the supports secure;
8) Write the frequency-avoidance check and damping into the installation card, because the root cause of vibration is near-frequency resonance with sparse supports, so installation must govern to prevent loosening.

Checklist

Reference

GB/T 17116.1-2018 Pipe supports and hangers

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL