E44-930 · Siphon and Backflow · Vessel · ★★★
Backflow, overpressure, hazard
[Mechanism] The backflow medium keeps entering the closed vessel, raising the pressure above the allowable value and creating an overpressure hazard.
[Calculation] A backflow of 0.3 m³/h enters the closed vessel, raising the pressure 0.05 MPa/h and exceeding the 0.4 MPa design limit in 8 h.
[Design Omission] No check valve, no pressure check, and no safety relief.
1) Install a check valve plus fast shutoff at the inlet (shut off on backflow), because backflow is the overpressure source and cutting it off stops the pressure rise, thereby preventing overpressure;
2) Provide a safety valve on the vessel (set ≤0.4 MPa, discharge ≥ twice the backflow rate), because it relieves on overpressure and keeps the vessel from bursting, thereby providing safety relief;
3) Check that the backflow rate matches the relief capacity (relief ≥0.6 m³/h > backflow 0.3), because a relieved margin keeps the pressure from rising, thereby stabilizing the pressure;
4) Fit the vessel with a pressure alarm (alarm at ≥0.35 MPa), because overpressure first shows as a pressure rise before the hazard, thereby monitoring the pressure for early warning;
5) Perform an overpressure test (verify the safety valve lifts), because the design omitted the relief check and the test confirms the lift pressure, thereby sizing the valve from data;
6) Provide level interlocking to close the valve on the backflow side, because a high level causes backflow and the interlock cuts off at once, thereby controlling the source to prevent overpressure;
7) Control the operating vessel pressure ≤0.35 MPa with an alarm, because a stable pressure prevents overpressure and controlling it prevents hazard, thereby keeping operation safe;
8) Write the check valve and safety valve into the vessel regulations, because the root cause of overpressure is backflow without relief, so the regulations must govern to prevent hazard.
GB/T 150.1-2011 Pressure vessels