E45-001 · Sensor Selection and Range · Oil pressure sensor CYB-1MPa · ★★
A pressure sensor with a 0~1 MPa range was used for a hydraulic impact with a measured 1.2 MPa peak; exceeding the range by 20% saturated and clipped the output, so the controller misjudged the pressure as only 1.0 MPa, the relief valve opened late and the actuator cylinder crept, slowing the cycle
[Mechanism] The sensor has a 1 MPa full scale and 120% overload capability; the measured 1.2 MPa peak exceeds full scale by 20% and enters the saturation region, clamping the output at the 20 mA upper limit.
[Calculation] The transfer function is nonlinear in the saturation region; clipping the peak loses 12% of the peak-to-valley span of the effective signal, giving a control deviation >15%.
[Design Omission] The range was not selected at working peak × 1.5 and neither peak hold nor a clipping alarm was provided; insufficient range margin causes saturation distortion.
① Range matching: the measured 1.2 MPa peak exceeds full scale by 20% → select a 0~2 MPa range (full scale ≥ peak × 1.5), leaving ≥50% margin so the impact peak is captured fully without clipping
② Peak hold: enable PEAK HOLD to latch the true 1.2 MPa peak → restore the peak-to-valley span clipped by saturation and reduce the setting deviation from >15% to ≤1%
③ Over-range alarm: warn when the output ≥90%FS → the relief valve switches to the high-flow circuit in advance, avoiding the late opening that makes the actuator cylinder creep
④ Overload capability: choose a model with overload capability ≥150% → withstand transient hydraulic overpressure without permanent shift
⑤ Limit pressure at the source: set the circuit-outlet relief valve to cap the system peak pressure ≤1.6 MPa → fundamentally avoid over-range and protect the sensor and valve
⑥ Three-point calibration: calibrate at full-scale 0/50%/100% to hold the linearity error ≤0.5%FS → ensure the reading is linear and does not shift
⑦ Commissioning verification: use an oscilloscope to record the impact waveform and measure the actual peak → confirm by data whether the range is adequate instead of relying on design estimates
⑧ Lock in selection: write the range × 1.5 selection rule into the sensor datasheet as a mandatory item → eliminate missed range selection causing saturation at the source
GB/T 15478-2015 Pressure sensor performance