E45-007 · Sensor Selection and Range · Pressure transmitter 4-20mA / DAQ card 0-10V · ★★
A 4-20 mA transmitter was wired directly to a 0-10 V DAQ card; the wrong range mapping made the reading only 50% of the true value, biasing control and leaving the valve under-opened
[Mechanism] 4-20 mA requires a 250 Ω sampling resistor to convert to 1-5 V; wiring it directly to a 0-10 V card makes 4 mA correspond to 0 V and 20 mA to only about 2 V (20% of range), halving the reading.
[Calculation] The DAQ card is calibrated for the full 0-10 V range, but actually only the 0-2 V segment is used, wasting 80% of the resolution.
[Design Omission] No sampling resistor was added and no range mapping was done; the signal types were mismatched.
① Sampling matching: put a 250 Ω precision resistor in the 4-20 mA loop to sample 1-5 V → then feed the 0-10 V card, restoring the correct mapping (direct connection made 20 mA correspond to only 2 V and halved the reading)
② Same-type direct connection: switch to a 0-10 V output transmitter that matches the DAQ card directly → same-type connection needs no conversion and avoids wiring errors
③ Software calibration: calibrate the DAQ card range (1-5 V ↔ 0-100%) → without calibration it computes on a 0-10 V basis; this makes the reading correct
④ Isolated conversion: use a signal isolator (4-20 mA→0-10 V) → long cable runs have large common-mode interference; this is stable and isolated
⑤ Full-point live test: verify on site that the full-point value corresponds to a true 100% → mapping errors cause bias; calibrate by actual measurement
⑥ Broken-wire detection: alarm when current <3.8 mA → a broken wire reads 0 and is misjudged as a low level; this gives a timely alarm
⑦ Wiring identification: mark brown +/blue - by color to prevent cross-wiring → cross-wiring burns the card; this ensures correct wiring
⑧ Lock in selection: write the signal type and sampling resistor into the I/O list as mandatory items → eliminate type-mismatch halving at the source
GB/T 17614 Transmitters