E45-006 · Sensor Selection and Range · Level transmitter two-wire 24VDC · ★★
A two-wire transmitter that should use 24 VDC was wrongly wired to 5 V; the output current was clamped to <4 mA and fluctuated, the level display lost its signal and the pump ran dry
[Mechanism] A two-wire 4-20 mA transmitter needs a ≥12 V operating voltage plus margin for loop voltage drop; a 5 V supply makes the internal regulator fail and clamps the output.
[Calculation] In the undervoltage region the transfer characteristic is distorted and the 4 mA lower limit is unstable, making the reading jump or drop to zero.
[Design Omission] The sensor's supply range was not checked and no power adaptation was provided; the voltage was mismatched.
① Supply matching: two-wire needs ≥12 V → supply 24 VDC (fluctuation ≤±10%) and check the loop voltage drop (line resistance × 20 mA + sensor drop ≤ supply − 12 V) to restore a linear 4-20 mA
② Power quality: choose a regulated supply and add filtering → suppress ripple that jitters the 4 mA lower limit and stabilize the zero
③ Intrinsic-safety current limiting: put an isolation barrier in the loop to limit voltage and current → meet intrinsic-safety requirements without undervoltage
④ Current verification: measure the loop current to confirm a continuous 4-20 mA (no-load ≥4 mA, full ≥20 mA) → verify the supply is sufficient and there is no signal loss
⑤ Low-voltage alarm: add a low-voltage alarm → undervoltage is a hidden fault; this finds it early
⑥ Polarity check: verify brown +/blue - when wiring to prevent reverse connection → avoid burning the circuit from reverse polarity and power up correctly
⑦ On-load live test: power up with load and measure the zero and full-point current → design values often deviate; confirm by actual measurement
⑧ Lock in wiring: write the supply range into the transmitter wiring diagram as a mandatory item → eliminate voltage-mismatch signal loss at the source
GB/T 17614 Transmitters