E45-012 · Sensor Selection and Range · Single pressure sensor critical unit · ★★★
A critical unit has only a single pressure sensor; sensor failure stopped the entire line for 4 h and caused lost production capacity
[Mechanism] When the single sensor fails, monitoring is lost; the system enters a safe shutdown with no backup data.
[Calculation] A single signal with nothing to compare against cannot identify its own fault; a bad value is taken as the true value.
[Design Omission] No dual-sensor voting or two-out-of-three logic and no fault diagnostics were provided; reliability is insufficient.
① Redundant configuration: add a backup sensor to the critical unit to make it dual-channel (originally single) → if one fails the other keeps monitoring without interruption (originally a single-point failure stopped operation for 4 h)
② Deviation comparison: alarm when the deviation between the two signals >5% → a single signal has no self-diagnostics and cannot identify a bad value
③ Two-out-of-three: use two-out-of-three voting at critical points → voting tolerates one bad signal and improves availability
④ Reasonableness diagnostics: alarm when a signal exceeds physical limits → bad values usually fall out of range and are self-detected
⑤ Automatic switchover: add fault-switchover logic that automatically cuts to the backup → manual switching is slow; this is seamless
⑥ Periodic comparison: compare the consistency of the two sensors monthly → drift is gradual and can be corrected early
⑦ Disconnect verification: test by disconnecting one sensor to verify switchover without stopping the line → designs often miss switchover; confirm by actual test
⑧ Lock in the policy: write the redundancy policy into the safety design document → eliminate non-redundant shutdowns at the source
GB/T 20438 Electrical/electronic/programmable safety