Knowledge Base › Electrical Sensor Error Case › Wrong Understanding of Differential-Pressure Range Burns the Capsule and Causes Permanent Shift

Wrong Understanding of Differential-Pressure Range Burns the Capsule and Causes Permanent Shift

E45-011 · Sensor Selection and Range · Differential-pressure transmitter 0-10kPa · ★★

Problem Description

A 0-10 kPa differential-pressure transmitter was misused for a 0-100 kPa air-pressure measurement; at 10 times the range the capsule plastically deformed and the reading shifted 30%, unrecoverable

Root Cause

[Mechanism] The measured 100 kPa is 10 times the range; overloading the capsule plastically deforms the elastic element and shifts the zero point by 30%.
[Calculation] Exceeding 3 times the range can cause a permanent, unrecoverable shift.
[Design Omission] The actual differential-pressure range was not checked and a 0-100 kPa range was not selected; the range was misunderstood.

Corrective Solution

① Range matching: the measured differential pressure is 100 kPa → replace with a 0-100 kPa transmitter (originally 0-10 kPa); the range stays within 3 times and the capsule does not plastically deform or shift 30%
② Overpressure protection: add a pressure-limiting valve/damper to suppress transient overpressure → water hammer in the air line causes transient overpressure; this protects the capsule
③ Overload capability: choose a model with ≥5x overload capability → occasional overpressure is unavoidable; this resists surges
④ Over-range alarm: alarm when the reading >95%FS → over-range damage is hidden; this detects it in time
⑤ Pressure test: apply pressure before installation to confirm linearity → deformation is irreversible; this finds defective units early
⑥ Slow-opening surge protection: add a needle valve in the pipe to open slowly → fast opening causes water hammer; this stabilizes pressure
⑦ Live calibration: calibrate the zero and full points → if deformation has shifted the output, a new calibration restores it
⑧ Lock in selection: write the differential-pressure range into the transmitter datasheet as a mandatory item → eliminate range-misunderstanding deformation at the source

Checklist

Reference

GB/T 17614 Transmitters

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »