E45-017 · Installation Position and Orientation · Radar Level Gauge on an Atmospheric Storage Tank · ★★
The antenna is tilted 8°, a fixed false echo appears, the level reading jumps ±50mm, and automatic control cannot be put in service
[Mechanism] Part of the energy within the beam angle strikes the tank wall at an angle and creates a spurious echo, which superimposes on the target echo and causes a misreading.
[Calculation] Beam angle θ = 8°; an 8° tilt sends a side lobe against the wall, the false echo reaches 30% of the true echo, and the distance solution is off by ±50mm.
[Design Omission] No leveling was done, no false-echo suppression was set, and no empty-tank calibration was made.
① Leveling: keep the antenna tilt <1° (was 8°) → the main beam points at the liquid surface, eliminating false echoes from the tilted wall strike
② Empty-tank calibration: calibrate the empty tank to build a false-echo map → fixed interference persists; have the software reject it
③ Echo threshold: set a threshold that suppresses interference below 30% of the true echo → the false echo is weak and no longer misleads
④ Guided-wave radar: switch to guided-wave radar to avoid wall reflection → free-space beams are wide; a guided probe is stable
⑤ Extended neck: add an extended neck so the beam spreads only after leaving the neck → distortion near the port; keep it clean
⑥ Recheck level: recheck the levelness each quarter → foundation settlement tilts it; correct it early
⑦ Level comparison: compare at 0 / 50% / full level → the false echo changes with level; calibrate over the full range
⑧ Make it stick: write the installation levelness into the radar installation card → eliminates unlevelled jumps at the source
GB/T 37905 Radar level gauges