Knowledge Base › Electrical Sensor Error Case › Shield Grounded at Both Ends Forms a Ground Loop and Drifts the Measurement

Shield Grounded at Both Ends Forms a Ground Loop and Drifts the Measurement

E45-029 · Cables and Drag Chains · 4-20mA Shielded Cable of a Pressure Transmitter · ★★

Problem Description

A 4-20mA shielded cable is grounded at both ends; a 2V potential difference between the two grounds drives a circulating current, drifting the reading ±0.3%FS and fluctuating as equipment starts and stops

Root Cause

[Mechanism] When the shield is grounded at both ends, the difference in ground resistance between the two points creates a ground potential difference that drives a circulating current in the shield; that current couples into the signal core and becomes differential-mode interference.
[Calculation] Ground potential difference V_g = 2V, shield resistance R_s = 2Ω, so the circulating current I = V_g/R_s = 1A; it induces ΔU in the core and offsets the reading by ±0.3%FS.
[Design Omission] The shield was not handled by the single-end grounding or equipotential principle, and the potential difference between the two grounds was not measured.

Corrective Solution

① Single-end grounding: ground the shield only at the signal source (transmitter) end → breaks the loop path and the drift disappears
② Potential measurement: measure the potential difference between the two grounds (<1V) before choosing the grounding method → avoids blind two-end grounding
③ Equipotential bonding: if both ends must be grounded, add an equipotential bonding conductor (≥4mm²) → forces equal potential and removes the difference
④ Make it stick: put the grounding method into the wiring diagram as a mandatory item → drawing-level control
⑤ Drift check: record the reading fluctuation during start/stop (≤0.1%FS) → verifies the circulating current is gone
⑥ Insulation: add insulating pads between the shield and the cable tray → prevents accidental multi-point grounding
⑦ Verification: disconnect one end ground and compare the drift → confirm by measurement that single-end grounding works
⑧ Training: add it to the wiring process card → prevents grounding both ends again