Knowledge Base › Electrical Sensor Error Case › Undersized Signal Cable Causes Excessive Voltage Drop and Sensor Undervoltage

Undersized Signal Cable Causes Excessive Voltage Drop and Sensor Undervoltage

E45-030 · Cables and Drag Chains · Two-Wire Transmitter on 0.5mm² Cable · ★★

Problem Description

A two-wire 4-20mA transmitter runs 300m on 0.5mm² cable; the round-trip voltage drop reaches 8.4V, above the allowed 4V, so the transmitter is fed only 15.6V, below its 18V minimum, and its output clamps and distorts

Root Cause

[Mechanism] Conductor resistance accumulates with length, and in a two-wire transmitter the supply and signal share one loop; too large a voltage drop puts the transmitter terminal voltage below its operating minimum and makes the output nonlinear.
[Calculation] R_cable = 2×300×0.0175/0.5 = 21Ω; voltage drop ΔU = I×2R = 20mA×42Ω = 8.4V; terminal voltage = 24−8.4 = 15.6V <18V.
[Design Omission] The loop voltage drop was not calculated, and the cable size was not increased or the supply raised for the distance.

Corrective Solution

① Larger conductor: switch to 1.5mm² cable → cable resistance drops from 21Ω to 7Ω, round-trip drop from 8.4V to 2.8V, terminal voltage ≥21V
② Supply: use a regulated 24VDC supply with ≥6V margin → keeps the terminal voltage ≥18V
③ Drop calculation: write ΔU = I×2R ≤4V into the selection table → eliminates undervoltage at the source
④ Distance limit: above 200m prefer 1.5mm² or a separate supply → long runs must be derated
⑤ Terminal-voltage check: with power on and loaded, measure the transmitter terminal voltage (≥18V) → confirm by measurement
⑥ Isolator barrier: put a barrier in the intrinsically safe loop to limit current while holding voltage → safe without undervoltage
⑦ Alarm: set a low-voltage alarm (terminal <18V) → makes hidden undervoltage show up early
⑧ Make it stick: put the cable-size-versus-distance table into the IO list as a mandatory item → drawing-level control

Checklist

Reference

GB/T 3369.1-2008 Analogue signals for process control systems