E45-043 · Cables and Drag Chains · Thin Drain Wire on Shielded Cable · ★★
The drain wire of the shielded cable is only 0.1mm², too thin; the high-frequency shielding effectiveness drops from 60dB to 35dB, and interference from a nearby VFD couples in and makes the reading jitter by ±2%
[Mechanism] The shield needs a drain wire with single-point grounding to form a low-impedance return path; a drain wire that is too thin gives high grounding impedance, so at high frequency the shield potential floats and shielding effectiveness drops.
[Calculation] A 0.1mm² drain wire has resistance R=0.0175/0.1×1=0.175Ω/m, and at 100MHz its inductive reactance is high, lowering shielding effectiveness by 25dB.
[Design Omission] The drain wire cross-section was not selected according to the shield current, and shielding effectiveness was not measured.
① Larger drain: change the drain wire to ≥0.5mm² → lower grounding resistance, shielding effectiveness restored to ≥55dB
② Cross-section check: specify the drain wire ≥1/3 of the shield's current-carrying capacity in the selection → gatekeeping at the source
③ Effectiveness test: measure the shielding effectiveness after installation (≥50dB) → confirm by measurement
④ Institutionalize: make the drain wire cross-section a mandatory item in the wiring diagram → drawing gatekeeping
⑤ Grounding: single-point ground the drain wire to the enclosure (low impedance) → clear return path
⑥ Coverage: choose a cable with braid coverage ≥85% → good shielding by itself
⑦ Routing: keep away from interference sources → less shielding needed
⑧ Maintenance: add to the EMC check card → inspect periodically
GB/T 18268.3-2010 EMC requirements for measurement and control equipment