E45-048 · Cables and Drag Chains · Unsupported, Unfixed Signal Cable · ★★
The signal cable hangs unsupported for 2m between the equipment and is not fixed; it swings with equipment vibration like an antenna and couples the 50Hz power frequency, making the reading jitter by ±1%
[Mechanism] A long unsupported cable acts as a large-loop antenna that readily couples the ambient electromagnetic field; swinging changes the loop area and makes the induced voltage fluctuate.
[Calculation] The loop area A varies by ±0.5m² as it swings; with a 50Hz field B=1mT the induced e=2πfBA≈0.3mV fluctuates, so the reading jitters.
[Design Omission] The cable routing was not fixed, and the loop area was not reduced.
① Fix the routing: secure the signal cable with clips every 0.5m → no swinging, stable loop
② Reduce the loop: route against a metal surface so the loop <0.01m² → lower induced e
③ Shielded twisted pair: switch to a shielded twisted pair with single-point grounding → common-mode suppression
④ Institutionalize: make the fixing spacing a mandatory item in the wiring diagram → drawing gatekeeping
⑤ Jitter test: measure the reading jitter after installation (≤0.2%) → confirm by measurement
⑥ Routing: keep away from high-current equipment → less coupling
⑦ Filtering: add a power-frequency notch at the receiver → suppress the residual
⑧ Maintenance: add to the monthly check list → inspect periodically
GB/T 18268.3-2010 EMC requirements for measurement and control equipment