Knowledge Base › Electrical Sensor Error Case › Lightning Surge Damages Module

Lightning Surge Damages Module

E45-092 · Signal Interference and EMC · Outdoor Temperature Transmitter · ★★

Problem Description

After a thunderstorm the input module of an outdoor transmitter is punctured and the reading pins at full scale

Root Cause

[Mechanism] Lightning induces a surge overvoltage on the signal line that travels along it into the module and, exceeding the withstand voltage, punctures the input.
[Calculation] The induced surge Up≈2kV (line-to-line) far exceeds the module's 0.5kV withstand voltage — 2kV is four times the limit — so the input is punctured and the energy permanently damages the module.
[Design Omission] No surge protective device (SPD) was installed, and there was no shielding and no grounding.

Corrective Solution

① Install an SPD: add a surge protective device at the signal-line entry (protection voltage ≤0.5kV) → clamps the surge so the module is not punctured
② Shielding and twisted pair: use shielded twisted pair outdoors with the shield grounded at both ends → reduces induction
③ Good grounding: run the SPD ground wire ≤1m straight to the ground electrode (resistance ≤10Ω) → effective discharge
④ Isolation: add signal isolation (≥1.5kV) → breaks the common-mode path
⑤ Multi-stage protection: two SPD stages, at the incoming line and inside the cabinet → staged discharge
⑥ Shielded enclosure: mount the transmitter in a metal rain-proof shielded box → blocks direct lightning induction
⑦ Verification by test: inject 2kV with a surge tester (module remains intact) → confirm
⑧ Institutionalize: write the SPD configuration into the lightning-protection drawing → gatekeeping

Checklist

Reference

GB/T 18802.21-2016 Low-voltage surge protective devices