Knowledge Base › Electrical Sensor Error Case › Housings Not Equipotential Cause Circulating Current

Housings Not Equipotential Cause Circulating Current

E45-098 · Signal Interference and EMC · Multi-Cabinet Signal System · ★★

Problem Description

The signal cable between the cabinets heats up, there is ±0.3℃ of crosstalk, and the shield hums with current

Root Cause

[Mechanism] The cabinets' housings are grounded at different potentials, forming a circulating current that flows along the shield and signal ground, introducing interference and heating.
[Calculation] With a ground potential difference ΔU=2V between the two cabinets and shield resistance R=0.1Ω, the circulating current I=ΔU/R=20A causes heating and ±0.3℃ of coupled crosstalk.
[Design Omission] The cabinets were not equipotentially bonded, were grounded at multiple points, and the shield was connected to different grounds at each end.

Corrective Solution

① Equipotential bonding: interconnect the cabinets with ≥16mm² copper bar (resistance ≤0.1Ω) → eliminates the potential difference, circulating current goes to zero
② Single-end shield: change the shield to single-point grounding → avoids ground loops
③ Signal isolation: add isolation to cross-cabinet signals → cuts the common mode
④ Unified grounding: bring the whole system to a single-point earth (resistance ≤4Ω) → no circulating current
⑤ Resistance reduction: treat the ground electrode to lower its resistance → stable potential
⑥ Measure the circulating current: use a clamp meter to measure the shield current (≈0) → confirmed
⑦ Verify by measurement: readings between the cabinets (crosstalk ≤0.05℃) → confirmed
⑧ Institutionalize: write equipotential bonding into the grounding diagram → gate at the source

Checklist

Reference

GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »