E45-101 · Signal Interference and EMC · PLC Control System · ★★
When a walkie-talkie is used on site, the PLC occasionally stops (2-3 times per shift)
[Mechanism] The walkie-talkie's strong near-field radiation couples into the PLC signal cables / cabinet seams, causing logic errors and a stoppage.
[Calculation] With a walkie-talkie transmit power of 4W, the near-field (0.5m) field strength E≈10V/m exceeds the PLC immunity (3V/m) and causes spurious trips and stoppage.
[Design Omission] The cabinet was not shielded, the signal cables were not shielded, and there was no filtering.
① Cabinet shielding: shield the PLC cabinet with continuous metal and conductive seam gaskets → shielding ≥40dB
② Shielded twisted pair: run all signal cables as shielded twisted pair with a 360° termination → suppresses coupling
③ Supply filtering: add an EMI filter to the PLC supply → blocks conduction
④ Separation: do not hold the walkie-talkie against the cabinet (≥1m) → reduces field strength
⑤ Isolation: add isolation to the I/O → better immunity
⑥ Watchdog: add a watchdog to the program to prevent spurious stops → self-recovery
⑦ Verify by measurement: PLC with the walkie-talkie transmitting near-field (no stoppage) → confirmed
⑧ Institutionalize: write cabinet EMC into the standard → gate at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test