E45-109 · Signal Interference and EMC · Contactor Coil and Sensor · ★★
When the contactor opens, the adjacent proximity sensor drops out momentarily (once per operation)
[Mechanism] Breaking the contactor coil produces a reverse high-voltage spike that radiates and couples into the sensor, making it drop out momentarily.
[Calculation] With coil inductance L=2H and current I=0.1A, the break-time reverse spike V=L·di/dt can reach several hundred volts; with MHz bandwidth it radiates and causes the sensor to drop out momentarily.
[Design Omission] No RC snubber across the coil, no freewheeling diode, and the sensor cable was not shielded.
① RC snubber: place an RC across the contactor coil (100Ω+0.1μF) → absorbs the reverse spike, less radiation
② Freewheeling diode: add a freewheeling diode to the DC coil → eliminates the reverse spike
③ Shielded twisted pair: run the sensor cable as shielded twisted pair → suppresses coupling
④ Separation: keep at least 200mm from the contactor → reduces field strength
⑤ Filtering: add a ferrite bead to the sensor supply → blocks conducted noise
⑥ Debounce: hardware debounce at the signal end → filters the spike
⑦ Verify by measurement: sensor with the contactor operating (no dropouts) → confirmed
⑧ Institutionalize: write coil snubbing into the standard → gate at the source
GB/T 17626.3-2016 Radiated radio-frequency electromagnetic field immunity test