Knowledge Base › Electrical Sensor Error Case › VFD Harmonics Distort the Supply

VFD Harmonics Distort the Supply

E45-111 · Signal Interference and EMC · Multiple VFDs on a Shared Bus · ★★

Problem Description

When several VFDs run together, the grid-side voltage THD rises to 15% and transmitter readings shift ±0.3%

Root Cause

[Mechanism] Harmonics from the multiple VFDs are injected into the grid, distorting the voltage, which couples through the supply into the sensor bridge voltage and shifts it.
[Calculation] With grid voltage THD=15% and sensor-supply PSRR=60dB, the output shifts ±0.3%; THD should be ≤5%.
[Design Omission] No line reactor was added, the supply was not isolated, and there was no filtering.

Corrective Solution

① Line reactance: add a DC reactor/AC reactor on the VFD feed → fewer harmonics, THD≤5%
② Independent supply: use an isolated regulated supply for the sensors → cuts the distortion
③ Active filtering: add an APF on the grid side → compensates the harmonics
④ High PSRR: choose sensors with PSRR≥80dB → suppresses ripple
⑤ π filter: LC π-filter at the supply input → stabilizes the supply
⑥ Isolation: isolate the signal → cuts common mode
⑦ Verify by measurement: readings with multiple VFDs at full load (shift ≤0.1%) → confirmed
⑧ Institutionalize: write harmonic mitigation into the standard → gate at the source

Checklist

Reference

GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields