E45-112 · Signal Interference and EMC · Single-Ended Pressure Transmitter · ★★
The reading of a pressure transmitter wired single-ended has ±0.4%FS mains-frequency noise superimposed on it
[Mechanism] A single-ended input provides no rejection of common-mode interference, so mains-frequency common mode turns directly into a differential reading.
[Calculation] With common-mode Vcm=3V and no CMRR on the single-ended input, it all converts to differential mode, giving ±0.4%FS; a differential CMRR≥100dB would suppress it 100×.
[Design Omission] A single-ended rather than differential input was used, with no isolation and no shielding.
① Go differential: convert the single-ended signal to a differential input with a differential converter → CMRR≥100dB
② Isolation: add an isolation amplifier (≥1kV) → cuts common mode
③ Shielded twisted pair: run the signal cable as shielded twisted pair → less common-mode pickup
④ Single-end grounding: ground the shield at one point → avoids ground loops
⑤ Mains notch: add a 50Hz notch filter → filters out the mains frequency
⑥ Balance: make the source-end impedances symmetric → suppresses common mode
⑦ Verify by measurement: readings in a mains-frequency field (≤0.05%FS) → confirmed
⑧ Institutionalize: write the differential requirement into the selection sheet → gate at the source
GB/T 17626.6-2017 Immunity to conducted disturbances induced by radio-frequency fields