Knowledge Base › Electrical Sensor Error Case › Excessive 24VDC Supply Ripple Causes 4mA Zero Jitter

Excessive 24VDC Supply Ripple Causes 4mA Zero Jitter

E45-125 · Power Supply · Pressure Transmitter · ★

Problem Description

The 4mA zero of the pressure transmitter jitters randomly between 3.82 and 4.18mA, a zero error of ±0.36mA (about 1.8% of full scale)

Root Cause

[Mechanism] Insufficient rectification and filtering in the switching supply superimposes high-frequency ripple on its output; the ripple voltage couples through the shared two-wire loop into the sensor's internal reference and amplifier, directly modulating the 4mA zero.
[Calculation] The measured supply ripple is Vr=200mVpp (rated ≤50mVpp); at a transmitter power-supply rejection ratio PSRR=80dB this works out to about 0.02mA of output fluctuation, but after coupling once more through the common ground the measured value is ±0.18mA, and the field jitter of ±0.36mA shows the ripple is amplified a second time.
[Design Omission] The supply was not a low-ripple type (rated ≤100mVpp but measured 200mVpp, out of tolerance), and no π filter was added on the sensor side, so ripple went straight into the zero.

Corrective Solution

① Switch to a low-ripple supply: output ripple drops from 200mVpp to ≤30mVpp → zero jitter tightens from ±0.36mA to within ±0.05mA
② Add a π filter at the sensor supply: a 10μH inductor plus 100μF/0.1μF capacitors on both sides → chokes the high-frequency ripple so the ripple entering the transmitter is ≤20mVpp
③ Independent isolated supply for the instruments: use a DC/DC isolated module for the sensors (24V input, 24V isolated output) → separates it from the power-supply ground and cuts the common-mode coupling
④ Add local decoupling capacitors at the supply: a 0.1μF ceramic plus a 10μF tantalum at each meter → absorbs local ripple so it does not travel down the long cable
⑤ Choose a high-PSRR transmitter: a type with PSRR≥90dB → cuts the output fluctuation by a further 3× at the same ripple
⑥ Measure the supply ripple with an oscilloscope: use a differential probe across the sensor terminals, Vrpp<50mV → confirm compliance with data
⑦ Single-point tie between the supply ground and the power ground: connect at only one point in the distribution cabinet → eliminates the common-mode ripple caused by ground potential difference
⑧ Ripple out-of-limit alarm: warn when Vrpp>80mV → detects supply aging in time

Checklist

Reference

GB/T 17626.4-2018