E45-126 · Power Supply · Flow Transmitter · ★
The 4-20mA transmitter supply is only 10.5V (≥12V required); the output clamps and stops rising beyond >16mA, so readings flat-top over the top 30% of the flow range
[Mechanism] A two-wire transmitter's operating voltage is Uw = supply Us − I×Rloop, where Rloop includes the cable resistance and the barrier current-limiting resistance; when Us is too low or Rloop too large, the drop eats the voltage until Uw < the minimum operating voltage Umin, internal regulation fails, and the output is clamped.
[Calculation] With Us=24V, a 200m run of 0.75mm² copper (R_cable=2×200×0.0235=9.4Ω) and a barrier current-limiting resistance Rg=50Ω, Rloop=59.4Ω; at full scale I=20mA the drop ΔU=1.19V, and the measured Uw=10.5V means Rloop is actually larger, or Us is only 18V and sags under load.
[Design Omission] The loop drop was not calculated: the 0.75mm² gauge was too small, the barrier current-limiting resistance was not included, and the supply's sag to 18V under load was not checked, so the output clamps on undervoltage at full scale.
① Calculate the loop drop: satisfy Us−I×Rloop ≥Umin+2V (Umin=12V) → pick the gauge or raise the voltage so full-scale Uw ≥14V
② Heavier signal cable: 0.75→1.5mm² takes R_cable from 9.4 down to 4.7Ω → the full-scale drop halves
③ Switch to a barrier with lower current-limiting resistance: Rg from 50 down to 20Ω → loop resistance drops 30Ω and full scale gains 1V of margin
④ Raise the supply voltage: from 18 to a regulated 24VDC → full-scale Uw rises from 10.5V to ≥16V, out of clamping
⑤ Power the instrument locally: shorten the supply distance so the line loss is <0.5V → stable far-end voltage
⑥ Measure the full-scale supply voltage: Uw ≥14V at a 20mA load → confirmed out of clamping
⑦ Choose a wide-input transmitter: 9-30V operating range → stays linear under the same drop
⑧ Make the loop-drop calculation a mandatory item on the wiring drawing: must be calculated before selection → gate at the source
GB/T 17614.1-2008