E45-127 · Power Supply · Intrinsically Safe Pressure Transmitter · ★
A pressure transmitter in the IS area misbehaves: its supply voltage is only 8V (≥12V required), the output drifts and occasionally zeros out
[Mechanism] A zener safety barrier limits energy by inserting a series current-limiting resistor in the loop, and that resistor together with the cable resistance forms the loop voltage drop; the smaller the current limit, the larger the series resistance and the lower the voltage available to the transmitter.
[Calculation] With a barrier current limit Imax=20mA and Us=24V, the energy-limiting series resistance Rs≈1200Ω gives a full-scale drop ΔU=20mA×1200=24V, leaving Uw≈0, so the IS supply must be raised or a low-resistance barrier chosen; the measured Uw=8V shows Rs is oversized with cable resistance added on top.
[Design Omission] The IS loop supply was not recalculated: the non-IS 24V design was reused, ignoring the barrier series resistance, and neither a low-resistance IS barrier was chosen nor the IS supply voltage raised.
① Choose a low-resistance IS barrier: series resistance from 1200 down to ≤600Ω → the full-scale drop halves and Uw rises
② Raise the IS supply: use a 28VDC IS supply (limiting still done by the barrier) → Uw rises from 8V to ≥16V
③ Use an isolated barrier: a DC/DC inside the barrier powers the transmitter independently → unaffected by the series-resistance drop
④ Calculate the IS loop drop: Us−I×(Rs+R_cable) ≥Umin+2V → must be calculated before selection
⑤ Choose a wide-input IS transmitter: 9-30V operating range → works with the same resistance
⑥ Measure the loaded IS voltage: Uw ≥14V at 20mA → confirmed sufficient
⑦ Match barrier and transmitter: barrier Imax ≥ transmitter Imax +20% → no current-limit clamping
⑧ Write the IS loop power calculation into the safety design document → gate at the source
GB 3836.4-2010