Knowledge Base › Electrical Sensor Error Case › Reversed Supply Polarity Burning Out the Transmitter Circuit

Reversed Supply Polarity Burning Out the Transmitter Circuit

E45-128 · Power Supply · Pressure Transmitter · ★

Problem Description

A replacement transmitter smoked and failed as soon as it was powered, and the other two transmitters on the same loop had no output; the wiring check showed the 24V brown and blue leads were reversed

Root Cause

[Mechanism] A two-wire transmitter's internal supply input has no reverse-polarity protection, or only a small series diode; on reversal the 24V lands directly on devices with inadequate reverse withstand and breaks them down, and the common ground path spreads the reverse voltage to the other transmitters on the bus.
[Calculation] The 24V reverse voltage across the internal LDO (reverse withstand −0.3V) is nearly a hundred times over → instant breakdown; a 1A Schottky in series would have survived, but the original design omitted it → direct destruction.
[Design Omission] The wiring had no polarity-error prevention: terminals lacked clear color or symbol markings, no transmitter with reverse-polarity protection was selected, and the polarity was not checked during installation.

Corrective Solution

① Terminal polarity marking: brown (+) / blue (−) per the IEC61158 color code, with labels → prevents misconnection
② Choose a transmitter with reverse-polarity protection: an internal blocking diode rated for a reverse 24V → survives reversal
③ Fuse plus blocking diode in the loop: a 1A self-resetting fuse on the bus and a parallel reverse-protection diode → on reversal the diode conducts and limits the voltage
④ Check polarity before wiring: use a multimeter to confirm brown to supply + and blue to − before power-up → no reversal
⑤ Independent protection on the shared bus: a small fuse ahead of each transmitter → one reversal does not affect the others
⑥ Installation briefing: mark the polarity on the wiring drawing and sign off on site → traceable responsibility
⑦ No-load voltage check before power-up: verify polarity before connecting the transmitter → avoids trial and error while live
⑧ Make reverse-polarity protection a mandatory item in the installation specification → gate at the source

Checklist

Reference

GB/T 33624-2017