E45-137 · Power Supply · Analog Acquisition Module · ★★
Multiple analog readings drift ±0.5% as grounded equipment operates, and the shield carries audible current
[Mechanism] The sensor supply is taken from a non-isolated source whose negative output ties to earth, and the acquisition card ground also ties to earth; the ground potential difference between them drives a loop current through the supply return that couples into the analog signal.
[Calculation] With a 1.5V ground potential difference (ΔU) and no isolation, that difference appears directly across the signal common → ±0.5% reading drift; adding DC/DC isolation (≥1.5kV) breaks the loop and cuts the drift to <0.05%.
[Design Omission] The sensor supply used no isolating DC/DC and ran straight off a non-isolated source, leaving the ground loop unbroken.
① Add an isolating DC/DC to the sensor supply: 24V in, 24V out isolated (≥1.5kV) → breaks the ground loop, drift <0.05%
② Single-point grounding: the system is earthed at one point only → removes the source of the potential difference
③ Separate analog and digital grounds: join them at one point → digital noise does not couple across
④ Single-ended shield grounding: ground at the source end only → no ground loop
⑤ Equipotential bonding: interconnect the cabinet ground bars (≤0.1Ω) → equal potential
⑥ Ground-potential measurement: equipment-to-equipment ground voltage ≤1V → confirmed no loop current
⑦ Drift measurement: reading while grounded equipment operates (drift ≤0.05%) → confirmed
⑧ Write the isolation requirement into the power drawing → gate at the source
GB/T 18268.1-2010