E45-136 · Power Supply · Pressure Transmitter · ★★
A pneumatic valve closing quickly dumped the load; the 24V bus surged to 34V for tens of ms and two transmitters were damaged by input overvoltage
[Mechanism] A switching supply driving a constant-current load has nowhere to dump the charge on its output capacitor when the load suddenly drops, so the bus voltage spikes; the supply feedback responds slowly, and the overshoot can exceed 140% of nominal and break down the transmitter.
[Calculation] With bus capacitance C=2200μF, a dumped current ΔI=2A over t=10ms, the overshoot ΔU=ΔI×t/C=2×0.01/0.0022=9V, which adds to the original 24V to reach 33V; the measured 34V is close to the transmitter's withstand limit.
[Design Omission] The supply had no overvoltage protection (OVP), its load-transient response was not sped up, and there was no voltage limiting ahead of the transmitter.
① Add OVP to the supply: choose a supply with overvoltage lockout → it shuts down above 30V and protects the transmitter
② Bleeder resistor on the bus: parallel a suitable dummy load → absorbs the capacitor charge on load dump, overshoot <28V
③ Limit the voltage ahead of the transmitter: a series zener / limiter module clamping at ≤30V → no breakdown
④ Faster supply response: choose a supply with a fast transient response → the overshoot halves
⑤ Split supplies: feed the transmitter and the valve controls separately → load dumps do not interact
⑥ Scope the load-dump overshoot: captured peak ≤28V → confirmed by measurement
⑦ Capacitor sizing: derate the bus capacitor to the load → less stored energy
⑧ Write the OVP requirement into the supply selection table → gate at the source
GB/T 17626.4-2018