Knowledge Base › Electrical Sensor Error Case › Long-Line Voltage Drop Starving the Far-End Supply

Long-Line Voltage Drop Starving the Far-End Supply

E45-148 · Power Supply · Remote Transmitter · ★★

Problem Description

A transmitter 200m away gets only 15V, with a low and unstable reading

Root Cause

[Mechanism] The resistance of a long thin line causes a large voltage drop; the far-end voltage is too low, so the transmitter becomes nonlinear and its reading drifts.
[Calculation] With 0.75mm² wire a 200m run has a round-trip resistance of 9.4Ω, and when several transmitters in parallel draw high current the far end falls below 15V; use 1.5mm² (4.7Ω) or power the transmitter locally.
[Design Omission] The long-line voltage drop was not calculated, the gauge was too small, and there was no local regulation.

Corrective Solution

① Heavier gauge: 0.75→1.5mm² halves the drop → far end ≥18V
② Local supply: add a local regulator module at the far end → no dependence on the distant feed
③ Raise the voltage: raise the near end to 28V → still enough at the far end
④ Drop calculation: near-to-far-end drop ≤2V → must be calculated before selection
⑤ Far-end regulation: insert a DC/DC regulator → constant voltage at the far end
⑥ Voltage measurement: at full load the far end reads ≥18V → confirmed
⑦ Segmented supply: feed the long line in sections → less drop per section
⑧ Write the drop calculation into the wiring drawing → gate at the source

Checklist

Reference

GB/T 17614.1-2008

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »
MOULDL · Mechanical Engineering Knowledge Base · free self-study reference for machine designers, 3D CAD models at MOULDL