E45-149 · Power Supply · kWh Meter / Metering · ★★
Running the VFD makes the kWh meter on the same bus read 8% fast
[Mechanism] The rectifier in the VFD draws harmonic currents that distort the grid voltage, and the kWh meter measures in error on the distorted waveform.
[Calculation] At THD=12% the kWh meter error reaches 8% once THD >5%; adding an input reactor or an APF brings THD to ≤5% and the error <1%.
[Design Omission] No input reactor was added, there was no filtering, and the meter was not a harmonic-tolerant type.
① Add an input reactor: fit a DC reactor on the VFD incoming line → fewer harmonics, THD ≤5%
② Active filtering: add an APF on the grid side to compensate the harmonics → accurate metering
③ Harmonic-tolerant meter: choose a wide-bandwidth kWh meter → error <1% under distortion
④ Separate buses: put the VFD and the metering on different buses → no mutual interference
⑤ Harmonic measurement: grid THD ≤5% → confirmed
⑥ Meter comparison: compare with a standard meter (difference ≤1%) → correct the offset
⑦ Isolation transformer: add an isolation transformer ahead of the VFD → isolate the harmonics
⑧ Write the harmonic mitigation into the distribution drawing → gate at the source
GB/T 14549-1993 Power quality — Harmonics in public supply networks