E45-152 · Power Supply · Current Transformer · ★★
Supply harmonics saturate the protection current transformer (CT), so the overcurrent protection trips spuriously
[Mechanism] The supply carries high-frequency harmonics that add harmonic content to the CT exciting current; the raised peak drives the core into saturation, the transformation distorts, and the protection trips spuriously.
[Calculation] The harmonics raise the equivalent peak by 20%, beyond the CT saturation knee → the transformation error >10% and the protection trips spuriously; filter the harmonics or choose a saturation-resistant CT.
[Design Omission] The harmonics were not filtered, the CT was given no saturation margin, and the effect of harmonics was not checked.
① Saturation-resistant CT: choose a CT with an air gap / a high saturation knee → no saturation under harmonics
② Harmonic filtering: add harmonic filtering ahead of the protection → the excitation does not overshoot
③ Margin calculation: size the CT with a 30% margin over the maximum harmonic peak → no saturation
④ Harmonic measurement: measure the current THD and check it against the knee → confirmed
⑤ Harmonic-immune algorithm: add harmonic suppression to the protection algorithm → no spurious trip
⑥ Reduce the harmonic source: add an APF upstream → cut it at the source
⑦ Spurious-trip review: the protection does not trip under harmonic conditions → confirmed
⑧ Write the CT selection into the protection drawing → gate at the source
GB/T 14549-1993 Power quality — Harmonics in public supply networks