E45-154 · Power Supply · Instrument Supply · ★★
Disturbance on the external grid (a neighboring arc furnace) makes the instrument reading fluctuate periodically
[Mechanism] No power-line filter was fitted on the incoming line, so conducted disturbance from the external grid goes straight into the instrument supply.
[Calculation] External disturbance conducted through the unfiltered incoming line is attenuated by only 6dB and increases the ripple on the instrument supply → reading fluctuation; an EMI filter with 30dB insertion loss suppresses it.
[Design Omission] There was no incoming EMI power-line filter, no shielding, and no isolation.
① Incoming EMI filtering: add a power-line filter (insertion loss ≥30dB) → the external disturbance is attenuated and the fluctuation disappears
② Isolation transformer: add one at the front end → isolates conducted interference
③ Shielded incoming line: run the incoming cable through metal conduit → less coupling
④ Separate bus: put the instruments and the disturbance source on separate buses → no cross-talk
⑤ Supply regulation: add a regulator → stable ripple
⑥ Disturbance measurement: compare reading fluctuation before and after the filter → confirmed
⑦ Grounding: bond the filter case directly to the cabinet → effective
⑧ Write incoming filtering into the supply drawing → gate at the source
GB/T 17626.6-2017