E45-155 · Power Supply · Absolute Encoder · ★★
A grid flicker (<100ms) drops the absolute encoder, and after re-powering the position offset is lost
[Mechanism] On a grid interruption the encoder loses power, and if the multi-turn count is held in volatile memory it is lost, so the position is wrong after re-powering.
[Calculation] A 100ms flicker de-energizes an encoder without battery backup → the multi-turn value is lost; a backup capacitor can ride through ≥200ms without loss.
[Design Omission] The encoder had no power-loss retention, no buffering, and the supply had no hold-up capacitor.
① Encoder power-loss retention: choose a backup-capacitor/battery type (retention ≥200ms) → a flicker does not lose the multi-turn count
② Bus hold-up capacitor: add 15mF at the supply → rides through 100ms without power loss
③ Supply UPS: give critical encoder points a small UPS → an interruption does not reset them
④ Position verification: compare against a reference point after power-up → reveals the offset
⑤ Re-homing: on offset, return automatically to the reference point → corrects it
⑥ Flicker test: simulate a 100ms interruption and confirm no loss → confirmed
⑦ Redundant supply: dual feeds to the encoder → one breaking leaves the other
⑧ Write retention design into the selection table → gate at the source
GB/T 7260.3-2003