E45-157 · Power Supply · Cross-Cabinet Signal System · ★★
The reading of a cross-cabinet signal drifts ±0.4% as equipment in another cabinet operates
[Mechanism] The negative ends of each cabinet 24V supply are tied directly to a common ground bar, so the ground potential difference between cabinets enters the signal as common mode through the shared supply return.
[Calculation] A 1V ground potential difference between cabinets enters the signal through the common ground → ±0.4% drift; isolating each cabinet supply cuts this path.
[Design Omission] The negative ends of multiple cabinet supplies were tied together, with no isolation and no equipotential bonding.
① Isolate each cabinet supply: use an isolated DC/DC for the cabinet-to-cabinet sensor supply → cuts the common-ground path so the drift returns to zero
② Equipotential bonding: interconnect the cabinet frames and ground-bar copper (≤0.1Ω) → equal potential
③ Signal isolation: add isolation to cross-cabinet signals → cuts the common mode
④ Single-point grounding: the system grounds at only one point → removes the source of the potential difference
⑤ Single-ended shield: ground the shield at one end only → no ground loop
⑥ Ground potential measurement: cabinet-to-cabinet ground voltage ≤1V → confirmed
⑦ Drift measurement: reading while another cabinet operates (drift ≤0.05%) → confirmed
⑧ Write cross-cabinet supply isolation into the drawing → gate at the source
GB/T 18268.1-2010