E45-158 · Power Supply · 24V Supply · ★★
The supply has run undervoltage (only 20V) for six months, and the transmitters slowly drift and occasionally read zero without being noticed
[Mechanism] With no voltage monitoring, the supply creeps down through aging or added load, and long-term undervoltage makes the transmitter linearity progressively worse and silently inaccurate.
[Calculation] The supply creeps from 24V down to 20V and the transmitter operating-voltage margin is used up → the linearity error grows to 2%; with no alarm it goes unnoticed for a long time.
[Design Omission] No online supply voltage monitoring or undervoltage alarm was provided.
① Online voltage monitoring: add a voltage transmitter or ADC to the supply → real-time voltage display
② Undervoltage alarm: warn when voltage <21V → early intervention
③ Trend logging: log the voltage curve → reveals a slow decline
④ Periodic calibration: calibrate the supply output quarterly → guards against aging drift
⑤ Margin design: keep the loaded supply ≥22V → headroom
⑥ Voltage measurement: measure the loaded output ≥22V → confirmed
⑦ Aging warning: remind at the supply end of life → pre-replace
⑧ Write monitoring and alarms into the O&M specification → gate at the source
GB/T 7260.3-2003