E45-159 · Power Supply · Simultaneous Power-Up of Multiple Supplies · ★★
Several supplies with large capacitors power up together, and the inrush current trips the branch breaker instantly
[Mechanism] The input capacitor of a switching supply is nearly a short at the instant of power-up; several powering up together produce an inrush current that exceeds the breaker instantaneous trip.
[Calculation] One unit draws 20A of inrush, and 10 units together draw 200A, above the branch breaker (32A) instantaneous trip; staggered power-up or soft start suppresses it.
[Design Omission] Power-up was not staggered, inrush was not limited, and the breaker was not a D-curve type.
① Staggered power-up: power up each supply 100ms apart → the inrushes offset and it does not trip
② Soft start: add input current-limiting soft start to the supply → inrush drops to 5A
③ D-curve breaker: choose a type D breaker tolerant of transients → no nuisance trip
④ Current-limiting resistor: put an NTC in series at the input → limits power-up current
⑤ Grouped supply: power up in batches → each batch inrush is manageable
⑥ Inrush measurement: power-up peak current ≤ breaker withstanding → confirmed
⑦ Snubber circuit: add a soft-start module at the input → smooth
⑧ Write the power-up sequence into the specification → gate at the source
GB 50054-2011