E45-160 · Power Supply · Dual Redundant Supply · ★★
Both supply paths fail one after the other, and with no alarm the operator does not know; the line stops silently
[Mechanism] Neither supply path gives status feedback when it fails, so maintenance does not know the redundancy is already lost; when the main path then fails everything stops.
[Calculation] The main path runs at 95% load and the backup is already dead but unreported → if the main fails everything stops; status reporting allows early backup replacement.
[Design Omission] The supplies had no fault alarm or status reporting, and there was no redundancy health monitoring.
① Fault alarm reporting: send supply fault signals to the PLC or HMI → immediate awareness
② Status indication: a run lamp per path plus remote status → visible
③ Health monitoring: report load rate/temperature → predicted
④ Automatic transfer: on main failure switch to the backup and alarm → no silent stop
⑤ Periodic self-test: weekly self-transfer test of the backup path → confirmed available
⑥ Redundancy test: break the main path and the backup continues automatically → confirmed
⑦ Maintenance work order: automatic dispatch on fault → timely replacement
⑧ Write the alarm design into the specification → gate at the source
GB/T 7260.3-2003