E45-161 · Power Supply · Sensor + DAQ Card · ★★
Powering the sensor before the data acquisition card makes the sensor self-check addressing fail, and all readings are 0
[Mechanism] After power-up the sensor handshakes with the DAQ card; if the card is not ready the handshake fails and the sensor enters an error state.
[Calculation] A wrong power-up interval makes the handshake window be missed → the sensor latches up with all zeros; the correct order, card first then sensor, avoids it.
[Design Omission] The power-up sequence was not specified, there was no handshake retry, and the order was wrong.
① Power-up sequence: power the DAQ card first and let it stabilize before the sensor → the handshake succeeds
② Handshake retry: the sensor automatically retries a failed handshake (3 times) → the window is not missed
③ Power-up delay: delay sensor power-up by 500ms → wait for the card to be ready
④ Status feedback: the sensor sends a ready signal back to the card → confirmed
⑤ Reset mechanism: send a reset command once the card is ready → the sensor reinitializes
⑥ Sequence test: power up in order and the readings are normal → confirmed
⑦ Power-cycle: automatically power-cycle after a wrong sequence → recovery
⑧ Write the sequence into the power-up specification → gate at the source
GB/T 18268.3-2010