Knowledge Base › Electrical Sensor Error Case › Supply Frequency Fluctuation Causing Speed-Measurement Error

Supply Frequency Fluctuation Causing Speed-Measurement Error

E45-163 · Power Supply · Synchronous Speed Measurement/Speed · ★★

Problem Description

The grid frequency fluctuates between 49.8~50.2Hz, and the synchronous speed reading is off by ±0.4%

Root Cause

[Mechanism] The synchronous method of speed measurement uses the supply frequency as its reference, so frequency fluctuation biases the speed reference.
[Calculation] A 0.4% frequency deviation offsets the synchronous speed reading by the same 0.4%; an independent crystal reference avoids it.
[Design Omission] The speed reference depended on the supply frequency and no independent time base was used.

Corrective Solution

① Independent time base: use a crystal reference for speed measurement → immune to mains-frequency fluctuation
② Frequency compensation: sample the grid frequency in real time and correct → compensates the offset
③ Encoder speed measurement: switch to incremental-encoder speed measurement → independent of supply frequency
④ Phase locking: phase-lock the time base to stabilize frequency → stable reference
⑤ Deviation measurement: reading under frequency fluctuation (deviation ≤0.05%) → confirmed
⑥ Software correction: compute speed from the real-time frequency → corrects the offset
⑦ Redundant reference: compare two references → guards against error
⑧ Write the time-base design into the specification → gate at the source

Checklist

Reference

GB/T 17626.7-2017

Related model download:Understood the principle and ready to try?Go to MOULDL to download related 3D models and CAD drawings for free »