E45-170 · Power Supply · Distribution Terminal Block · ★★
A distribution-cabinet terminal block heats up and discolors, and the instruments connected to it lose power intermittently
[Mechanism] Insufficient terminal screw torque or a mismatched wire gauge makes the contact resistance high; the joint heats and oxidizes, and contact breaks and remakes intermittently.
[Calculation] With a contact resistance of 0.1Ω at 20A the heating P=I²R=40W raises the terminal temperature until it discolors, and oxidation increases the resistance → intermittent loss; tightening to the specified torque prevents it.
[Design Omission] The terminals were not torqued, were not inspected, and the current rating did not match.
① Torque tightening: tighten the terminals with a torque wrench → low contact resistance, no heating
② Current-rating match: match the wire gauge to the terminal rated current → no overheating
③ Periodic inspection: measure terminal temperature with an IR camera (≤60℃) → early detection
④ Tinning: tin the wire ends → lower contact resistance
⑤ Redundant wiring: double terminals on critical circuits → if one loosens the other continues
⑥ Temperature-rise measurement: terminal temperature ≤60℃ at full load → confirmed
⑦ Anti-loosening: add spring washers under the screws → they will not loosen
⑧ Write the inspection interval into O&M → gate at the source
GB 50054-2011