E45-169 · Power Supply · Switching Supply · ★★
At light load the switching supply outputs 25.5V (rated 24V), and the transmitter reads 0.5% high
[Mechanism] At light load the feedback duty cycle of the switching supply goes out of regulation and the output voltage runs high, which biases the transmitter bridge voltage and offsets the reading.
[Calculation] The no-load output of 25.5V is 6% above rated, and the transmitter bridge bias makes the reading off 0.5%; adding a minimum dummy load brings the voltage back to 24V.
[Design Omission] The supply had poor light-load behavior, no minimum load was added, and it was not calibrated.
① Add minimum load: put a dummy load (≥5% of rated) on the supply output → the light-load voltage returns to 24V
② Choose a wide-load supply: pick a type regulated within ≤1% from 20% to 100% load → no light-load drift
③ Output calibration: calibrate the light-load point voltage at the factory → accurate
④ Voltage monitoring: measure the light-load output ≤24.5V → confirmed
⑤ Permanent dummy load: keep the minimum load on critical supplies at all times → stable
⑥ Reading verification: reading deviation ≤0.1% at light load → confirmed
⑦ Derating design: size the supply for the actual load → it never runs light
⑧ Write light-load behavior into selection → gate at the source
GB/T 7260.3-2003