E45-168 · Power Supply · Same-Bus Instruments · ★★
Starting and stopping a large motor on the same bus makes the readings of nearby instruments jitter by ±0.3%
[Mechanism] Starting and stopping a large machine produces a voltage sag and harmonics that conduct through the shared bus to the instrument supply and make its readings jitter.
[Calculation] Start/stop causes a 10% bus voltage drop, and the added harmonics increase the ripple on the instrument supply → ±0.3% jitter; a separate bus plus isolation suppresses it.
[Design Omission] The large machine and the instruments shared a bus, with no isolation and no filtering.
① Separate buses: put the large machine and the instruments on separate buses → interference is cut
② Isolated instrument supply: use an isolated regulated supply for the sensors → it does not sag with the bus
③ Bus filtering: add an EMI filter at the instrument bus entry → suppresses harmonics
④ Soft start: add a soft starter to the large machine → less voltage drop
⑤ Hold-up capacitor: add capacitance at the instrument end → rides through the sag
⑥ Jitter measurement: jitter ≤0.05% during large-machine start/stop → confirmed
⑦ Harmonic mitigation: an APF ahead of the large machine → at the source
⑧ Write bus separation into the distribution drawing → gate at the source
GB/T 17626.4-2018