E45-167 · Power Supply · VFD · ★★
When the upstream voltage sags, the VFD reports an undervoltage fault and shuts down, which also drops the associated instruments
[Mechanism] The VFD DC-bus voltage falls with the grid sag, and once it drops below the undervoltage point it triggers a protective shutdown.
[Calculation] A 30% grid dip drops the DC bus from 540V to about 380V < the 400V undervoltage threshold → trip; a DC reactor or boost circuit can ride through it.
[Design Omission] The VFD had no undervoltage ride-through, no DC support, and the grid had no voltage regulation.
① DC support: add support capacitors or a boost chopper to the bus → the sag does not punch through
② Undervoltage ride-through: set an undervoltage trip delay or widened threshold → short sags do not trip
③ Line voltage regulation: add a regulator upstream → a stable bus
④ DC reactor: add a DC reactor → suppresses the dip
⑤ Staged shutdown: only the VFD stops, the associated instruments keep running → less loss
⑥ Sag test: verify no trip per GB/T17626.11 → confirmed
⑦ Grid mitigation: an upstream APF or regulator → at the source
⑧ Write sag ride-through into the VFD parameters → gate at the source
GB/T 17626.11-2008