E45-166 · Power Supply · UPS Battery · ★★
When the mains fails the backup battery is already depleted, so the UPS transfer fails and all instruments stop
[Mechanism] The battery sat on float charge for a long time without capacity maintenance, so its plates sulfated and the capacity dropped sharply; when discharge was needed the terminal voltage collapsed and could not support the load.
[Calculation] A nominal 100Ah battery has only 30Ah left from sulfation, and under load the discharge terminal voltage falls from 12V to 9V within one minute < the inverter threshold → transfer failure.
[Design Omission] No periodic discharge maintenance was done, capacity was not measured, and the battery was not replaced at end of life.
① Periodic discharge maintenance: run a capacity discharge test quarterly → prevents sulfation and reveals capacity
② Capacity monitoring: measure internal resistance/capacity online → warns of depletion
③ End-of-life replacement: pre-replace batteries at end of life (3~5 years) → no sudden failure
④ Temperature compensation: adjust the float voltage with temperature → extends life
⑤ Redundant batteries: parallel strings add capacity → one bad string does not fail the system
⑥ Transfer drill: simulate a mains outage and verify the transfer succeeds → confirmed
⑦ Alarm reporting: low-capacity battery alarm → advance warning
⑧ Write the maintenance interval into the O&M specification → gate at the source
GB/T 19638.1-2014 Stationary valve-regulated sealed lead-acid batteries