E45-165 · Power Supply · 24V Switching Supply · ★★
An intermittent short in one transmitter trips the overcurrent protection of the whole 24V supply, and every instrument on the branch loses power
[Mechanism] The supply overcurrent threshold is set too low and is not graded, so a single-point short trips the main supply protection and cuts off the whole branch.
[Calculation] The supply is rated 10A, and a short in one transmitter spikes the current to 15A above the protection point → the whole branch trips; a small branch fuse (0.5A) would drop only the faulty transmitter.
[Design Omission] No graded protection, the main supply fed multiple transmitters directly, and there was no branch current limiting.
① Graded protection: main supply plus a branch fuse (0.5A) per transmitter → a single short drops only that transmitter
② Threshold setting: set the main supply overcurrent point at 1.25× the total → no misoperation
③ Fault isolation: isolate a shorted transmitter automatically without affecting the others → the whole branch stays up
④ Current-limiting module: series current limiting per branch → a fault is limited and does not trip the main
⑤ Alarm and location: an independent alarm for whichever transmitter shorts → fast diagnosis
⑥ Short-circuit drill: simulate a single-transmitter short and verify the rest stay normal → confirmed
⑦ Margin design: supply rating ≥1.25× total load → stable
⑧ Write graded protection into the distribution drawing → gate at the source
GB 50054-2011