E45-175 · Grounding and Shielding · PLC Analog Input Module · ★★
The zero point of a 4-20mA analog channel drifts ±0.8mA as the motor starts and stops; at the grounding bar there is a 1.2V AC potential difference between the signal ground and PE
[Mechanism] The signal ground (SG) is wrongly tied to the protective earth (PE) at one point in the cabinet; the PE between devices develops a potential difference from load current, forming a ground circulating current that flows along the signal return and adds to the millivolt-level signal.
[Calculation] Ground circulating current I=ΔU/R with ΔU=1.2V and R=0.5Ω → I=2.4A; across a 100Ω signal source impedance it drops 0.24V ≈ 1.2%FS signal drift.
[Design Omission] SG and PE are not isolated beyond a single point; the analog system ground is tied straight to PE, forming multi-path circulating current.
① Single-point grounding: connect the signal ground to PE at one designated point through isolation → cuts the ground circulating-current path
② Floating acquisition: use an isolator on the analog channel so SG and PE are not directly connected → the ground potential difference cannot couple in
③ Isolated transmitter: add a signal isolator at the front end (withstand voltage 1500V) → decouples signal and ground
④ Star collection: gather all SG at a single star point on the grounding copper bar → avoids multi-path circulating current
⑤ Ground potential difference test: measure the AC voltage between SG and PE when powered <1V → verify no circulating current
⑥ Shielded twisted pair: use shielded twisted pair with the shield grounded at one end → suppresses common mode
⑦ Inter-cabinet equipotential: bond the cabinets with ≥16mm² copper bar → equalizes potential
⑧ Grounding diagram specification: make the signal-ground / protective-earth wiring a mandatory item in the grounding diagram → gate at the source
GB/T 2887-2011 General specification for computer field