E45-176 · Grounding and Shielding · 4-20mA Signal Cable · ★★
After both ends of the shielded signal line were bonded to PE, the signal carries 50Hz mains-frequency ±0.5mA, and the greater the distance between the two cabinets the stronger the noise
[Mechanism] With the shield bonded to PE at both ends, if the two grounding points differ in potential a longitudinal circulating current flows in the shield, and that current induces a common-mode voltage in the twisted-pair loop that an imbalance converts into differential-mode noise.
[Calculation] Grounding-point potential difference ΔU=2V across a shield resistance R=0.3Ω → circulating current I=6.7A; on 100m of cable it induces e=2πf·M·I with M≈0.1μH/m → e≈20mV ≈ 1% of the signal.
[Design Omission] The frequency-based rule of single-end shield grounding at low frequency and both-end grounding at high frequency was not followed; all shields were grounded at both ends.
① Low-frequency single-end grounding: for a 50Hz signal bond the shield to PE at the source end only → cuts the shield circulating current
② Both ends only for high frequency: ground both ends only for signals >1MHz on short cables → the frequency-based rule
③ Both ends via capacitor: when both ends must be grounded, bond through a 10nF capacitor → passes high frequency, blocks the mains-frequency circulating current
④ Equipotential to lower the difference: add an equipotential copper bar between the cabinets to keep ΔU<1V → reduces the circulating current
⑤ Shield resistance test: measure the shield DC resistance <1Ω/100m → verify continuity
⑥ Common-mode rejection: use a differential input (CMRR>90dB) → little common-to-differential conversion
⑦ Noise comparison: measure the signal peak-to-peak before and after breaking the shield loop → verify the improvement
⑧ Write the grounding principle into the wiring rules → gate at the source
GB 50217-2018 Standard for design of cables of electric power engineering