E45-178 · Grounding and Shielding · Field Sensor Grounding Electrode · ★★
After a lightning surge several transmitters break down; the grounding electrode resistance measures 28Ω (≤4Ω required)
[Mechanism] With a high grounding electrode resistance R, the lightning current I produces a high potential U=IR at the electrode; discharge is slow and the electrode potential rises, back-flashing through the signal cable into the equipment; a high R also raises the impedance of the discharge path and the residual voltage.
[Calculation] Lightning current I=10kA with R=28Ω → electrode potential U=280kV; with R=4Ω → U=40kV, a 7× lower back-flash risk.
[Design Omission] The grounding electrode is shallow, the soil resistivity is high, and no resistance-reducing agent or vertical electrode array was used.
① Resistance-lowering electrodes: add a vertical electrode array (angle steel 50×5, L=2.5m × 4 radiating) → lowers R to ≤4Ω
② Resistance-reducing agent: fill bentonite-based agent around the electrode → improves contact resistance
③ Deep burial: bury the horizontal grounding conductor ≥0.8m deep → stabilizes moisture and lowers R
④ Equipotential bonding: connect the equipment PE to the grounding electrode directly with ≥25mm² copper cable → low-resistance discharge
⑤ Surge protection: add an SPD at the signal port (residual voltage ≤40V) → clamps the back-flash
⑥ Resistance test: measure R≤4Ω with a grounding resistance meter → verify compliance
⑦ Seasonal factor: re-test in the dry season to catch R rising again → long-term stability
⑧ Write the grounding design into the lightning-protection specification → gate at the source
GB 50057-2010 Design code for protection of structures against lightning