E45-182 · Grounding and Shielding · Thermocouple Extension Wire · ★
The K-type thermocouple reading carries random noise of ±2℃; no shield is used, or the shield is left floating
[Mechanism] With no shield, or with both ends of the shield floating, the wire acts like an antenna and picks up ambient electromagnetic fields (VFDs, welding), and the noise adds to the millivolt thermoelectric voltage as common mode; a floating shield itself also floats and has no shielding effectiveness.
[Calculation] Field strength E=10V/m, bare wire 5m long, effective height 0.1 → induced e=E·h on the order of 1V, far larger than the thermocouple's 40μV/℃ (2℃≈80μV) → it completely drowns the signal.
[Design Omission] The weak thermocouple signal uses no shielded wire, or the shield is not effectively grounded.
① Shielded wire: switch to shielded extension wire → resists ambient coupling
② Single-end grounding: bond the shield to PE at the receiving end only → provides a shielding reference
③ Twisted pair: use twisted pair for the signal → little common-to-differential conversion
④ Away from interference sources: keep the cable >30cm from the VFD → lowers field strength
⑤ Conduit: run the weak-signal line in grounded metal conduit → secondary shielding
⑥ Filtering: add an RC low-pass at the front end (cutoff 10Hz) → suppresses high-frequency noise
⑦ Noise test: measure the signal peak-to-peak <50μV → verify it is clean
⑧ Write the shielding requirement into weak-signal routing rules → gate at the source
GB/T 16839.1-1997 Thermocouples - Part 1: Reference tables